Severity: Notice
Message: Only variable references should be returned by reference
Filename: core/Common.php
Line Number: 257
Ratings | Input: 48VDC | Output: 120VAC Power: 5kVA |
---|---|
Applicable standards | IEC 61000-4 / FCC part 15 / cULus 1778 Listed / RoHS |
Cooling / isolation DC/AC | Forced |
Efficiency (typical) | Enhanced power conversion: 95% On line: 91% |
Dielectric strength DC/AC | 4,300VDC |
Vibration | GR63 office vibration 0 – 100hz-0.1g Transport vibration 5-100Hz 0.5g 100 – 500hz-1.5g Drop test |
Altitude above sea level | <1500m; no derating >1500m; 0.8% / 100m derating |
Operating temperature | -20 – 40 C; -4 – 104°F for rated power 40 – 65°C with 2%/°C derating 104 – 149°F with 1%/°F derating |
Ambient / storage temp / relative humidity | -40 – 70°C (-40 – 158°F) |
Relative humidity | 95%, non-condensing |
Operating ambiance / ingress protection | Free from dust and corrosive materials / NEMA 1 |
Material (casing) | Coated steel-ALU ZINC |
The Y-One is an upscale stand alone inverter providing a pure sine wave AC supply. It is the corner stone of an AC backup solution compatible with any kind of DC Power system. At the leading edge of conversion technology it operates with superior efficiency with no compromise in quality and performance.
The “Twin Sine Innovation” (TSI) technology is designed to empower Business Continuity Solutions with great value for money. Optional Manual ByPass available for module live replacement.
Related Products